Code Clarifications and Corrections |
| The following are clarifications or corrections, by section, to the 2002 Oregon Manufactured Dwelling and Parks Specialty Code. |
Sign up for Code Clarifications and Corrections updates by e-mail |
| |
| 1-11.1(d) Direct supervision is considered to be 85% of the time. |
| 1-9.7(d) Lost HUD labels may only be reissued by the manufacturer of the home. The Building Codes Division can no longer issue replacement labels. |
| 3-2.4.2
Floodways. This section has been amended by Temporary Administrative Rule 918-500-0021. |
| 3-2.5.2 Seismic Zone 3. A home installed in seismic Zone 4 is only required to be anchored if the home exceeds 3 feet in height for 75% of the main frame piers. |
| 3-2.5.3 Seismic Zone 4. A home installed in seismic Zone 4 is only required to be anchored if the home exceeds 2 feet in height for 75% of the main frame piers. |
| 3-5.2(f) Precast concrete masonry units are considered to be capable of holding 15,000 pounds. |
| 3-9.8(c) CMU footings shall be 12 inches x 5 ½ inches deep concrete. |
| 3-9.9(d) ICF footings shall be 12 inches x 5 ½ inches deep concrete. |
3-12.2 Temporary steps. Only one set of temporary steps is required. |
| Table 3-B A concrete runner or slab is considered equal to 2300 psf soil. |
| Table
3-B Note: 10 foot wide homes are not required to be perimeter supported except at the doors and any opening greater than 48 inches. |
| 4-3.4(c) Factory installed service equipment is not required to contain a means for connecting accessory buildings, accessory structures, or additional electrical equipment located outside a manufactured dwelling. This is an interpretation by HUD. |
| 4-4.4(b) Self drilling or self tapping screws are acceptable as paint penetrating bonding devices. |
| Table 4-B In the 200 Amp grounded conductor aluminum column, the wire size should be #2/0 |
| Table 4-B Note 1 The THHN wire should be THHW |
| Table 5-C Add note 3. PVC, ABS, and PE pipes are only allowed outside of the building line. |
| 6-3.10 When a water heater pan is installed, the pan shall be drained outside of the skirting line. The pressure/temperature
relief piping cannot be terminated into the pan, it must terminate beneath the home. |
| Chapter 8 Decks must not be supported by the home and must not be secured tightly to the exterior siding. |
| 8-4.4(d) Cementitious board may be used as an equivalent fire resistive material. Consult with the authority having jurisdiction. |
| 9-5.3(k) Has been amended by OAR 918-500-0021 |
| 9-6.3(n) Has been amended by OAR 918-500-0021 |
| Table 9-A Has been amended by OAR 918-500-0021 See the amended Table in the web site edition of the Manufactured Dwelling and Park Specialty Code. |
| Table 9-B Has been amended by OAR 918-500-0021 See the amended Table in the web site edition of the Manufactured Dwelling and Park Specialty Code. |